| Rated Voltage | 3.3kV or 6.6kV |
| Busbar Thermal Rating | 800,1250, 200 or 4000 A rms |
| Busbar Short Time Withstand | 50kA for 1 sec for 800A or 50kA for 3 sec for 1250 to 4000A |
| Busbar Peak Withstand | 125kA peek |
| Enclosure Protection | IP4X |
| Power Frequency Rating | (1 min) 20kV rms |
| Rated Circuit Operational Current | 400A rms |
| Contactor AC4 Rating | 400 A rms |
| Breaking Current | 4kA rms |
| Making Current | 4kA rms |
| Motor Max Rating | 1500kW at 3.3kV or 300kW at 6.6kV |
| Transformer Max Rating | 2000kVA at 3.3kV or 4000kVA at 6.6kV |
| Capacitor max Rating | 2000kVAr at 3.3kV or 4000kVAr at 6.6kV |
| Impulse Rating | 40/60kV peek |
| Slendaur
High Voltage Fused Backed Vacuum Contactor Switchgear (Portable
Document Format) LSE_Slendaur.pdf [516Kb] [download now] |
|
SLENDAUR High Voltage Starters
3.3kV and 6.6kV Fuse Protected Vacuum Contactor Unit
The
SLENDAUR range of fuse protected vacuum contactor units is of the
single tier withdrawable pattern, suitable for connection to
breakers or isolators for the complete switchboard format.
The fixed housing incorporates phase segregated busbars,
fast make earth switch and individual HV and LV Outgoing cable
chambers.The truck withdraws on nylon wheels and incorporates fully
segregated LV and HV components, to allow safe and unrestricted
access for testing and maintenance purposes.
A comprehensive
system of mechanical interlocks in provided between truck, isolator,
contactor, earth switch and LV compartment door.
Main Features
- Arc Fault Containment to IEC298 Appendix AA (optional)
- Type C Co-ordination to IEC632-1 Appendix B
- Busbar Fault Capability to IEC694
- EMC & RFI to CISPR & EN55011
- Fully Withdrawable
- Reversing, Star Delta, Auto Transformer, Stator & Rotor Starting
- Phase to Phase and HV to LV Segregation
- Non Insulated or Insulated Busbar Systems