The
Anglo Valve offers many innovative and unique features, ensuring maximum
performance, whilst maintaining customer confidence.
The
main features are:
|
The
Anglo stored pressure valve can be rotated after pressurisation to ensure
the discharge hose can be realigned with the nozzle retainer and that the
pressure gauge is always facing the front. | |
|
The
revolutionary spindle valve enables the extinguisher to be pressurised
without depressing the spindle, eliminating the possibility of powder
contaminating the 0 rings, therefore accelerating the recharging
procedure. | |
|
The
pressure gauge can be checked during the annual service, using a magnet.
This renders obsolete the requirement to remove or pierce the gauge
glass. |
This
has two advantages:
|
Increased
speed in servicing; | |
|
Most
importantly, a non-invasive technique removes the possibility of
moisture/dirt ingress which increases the reliability of the internal
components. |
Further
features include corrosion resistant brass valve body, stainless steel spring
and safety pin.
COLOUR
CODING
The Anglo Range of hand portable fire extinguishers has been assessed and approved to BS7863: 1996, which requires an area of 3% to 5% of the body being colour coded to indicate the extinguishing media contained in the extinguisher.
WATER,
the most
commonly used extinguishant for class A fires only, involving carbonaceous
materials such as wood, paper, textiles. Water extinguishes fires by cooling the
fire, removing the heat needed to sustain combustion and preventing remaining
embers from re-igniting.
TRICLASS,
fire
extinguishers, with an AFFF additive, have the effect of enhancing its class
A fire fighting ability and also enabling it to be used on class B
(liquid fires) very successfully. TRICLASS extinguishers feature a unique nozzle
which ensures operator safety if in accidental contact with live electrical
equipment, (complies with electrical conductivity test specified in BS EN 3-2:
1996. clause 4, Annex A).
ABC
Dry
Powder extinguishers are extremely efficient on class A fires, they
are also used on class B and class C fires (Gaseous). (There is no
test to determine class C fires specified in BS EN 3). In addition they
can also be used on live electrical equipment.
CARBON
DIOXIDE (C02)
is
used on class B fires. It can be safely used on live electrical equipment.
C02 is extensively used throughout the food industry for its cleanliness in
application.
| EXTINGUISHANT | Water | AFFF | ABC Dry Powder | Carbon Dioxide | ||||
| CAPACITY | 9 Litres | 6 Litres | 9 Litres | 4kg | 6kg | 9kg | 2kg | 5kg |
| ORDER CODE | XAW9 | XAF6 | XAF9 | XAPA4 | XAPA6 | XAPA9 | XAC2SH | XAC5HH |
| PAINT FINISH/COLOUR | Polyester Red (RAL 3000) | Enamel | ||||||
| LINING | Polymer Coating | |||||||
| FIRE CLASS | A | A.B.+ Electrical Safety Test | A.B.C. Types + Electrical | B. and Electrical | ||||
| FIRE RATING | 13A | 13A/144B | 21A/183B | 13A/113B | 27A/183B | 34A/233B | 34B | 55B |
| OPERATING TEMP | +5 C to +60 C | -20 C to +6O C | ||||||
| TEST PRESSURE | 23 Bar | 200 Bar | ||||||
| OPERATING PRESS @ 200C | 12 Bar | 50 Bar | ||||||
| AVE. DISCHARGE DURATION | 70s | 38s | 58s | 17s | 18s | 23s | lOs | 15s |
| DISCHARGE RANGE | 6m | 4m | 4m | 5m | 5m | 7m | 3m | 3m |
| SAFE OPERATING DISTANCE |
2 metres |
|||||||
| CYLINDER |
1.6mm Mild Steel Grade CR1 and CR3 BS 1449 |
Steel to BS 5045 pt.1. |
||||||
| OPERATING VALVE |
Brass Hot Stamping (BS2872 Grade CZ122) |
Brass Hot Stamping |
||||||
| HANDLES | Mild Steel | |||||||
| HEIGHT | 588mm | 542mm | 588mm | 450mm | 542mm | 588mm | 585mm | 710mm |
| DIAMETER | 190mm | 162mm | 190mm | 162mm | 162mm | 190mm | 100mm | 140mm |
| FULL WEIGHT | 14.4kg | 10.4kg | 14.4kg | 7.5kg | 10.4kg | 14.4kg | 6.9kg | 13.4kg |
| EMPTY WEIGHT | 5.35kg | 4.3kg | 5.35kg | 3.4kg | 4.3kg | 5.35kg | 4.9kg | 8.4kg |
| CARTON SIZE | 197x197x587 | 180x180x550 | 197x197x587 | 180x180x455 | 180x180x550 | 197x197x587 | 175x147x610 | 199x177x730 |
| APPROVED TO BS EN 3 | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
![]() |
![]() |
![]() |
![]() |
Water |
Foam |
Dry Powder |
CO2 |
In the interest of product improvement we reserve the right to amend this specification without prior notice